B3x Operation Mode
All B3x controllers, who support B3x operation mode, will have these features.
Hardware features | Functions |
---|---|
Real-time clock | To trigger the night mode when pre-configured timing is time out. |
Keycard input |
To receive a input signal when guest has inserted the keycard into keycard switch. Besides physical input point, a MODBUS command can activate this point. |
Check-in input |
To receive a input signal from Room Control System when guests have been checked-in in lobby. Besides physical input point, a MODBUS command can activate this point. |
Window input | To trigger the interlock mode when window is open. |
B3x Operation Mode | Details |
---|---|
Pre-cooling |
When 'Check-in' input signal is switched from OFF -> ON, FCU will go into the mode. Set a low temperature to chill the room faster during guest check-in. Default: Disabled. |
Welcome |
When 'Keycard' input signal is switched from OFF -> ON and it is in pre-cooling mode, FCU will go into the mode. Set a comfortable temperature when guest enters the room for the first time. Default: Disabled. |
Un-occupied |
When 'Keycard' input signal is switched from ON -> OFF, FCU will go into the mode. System moderate the temperature for energy saving when guest leaves the room. Default: Enabled, Cooling mode, 26oC, Low fan speed. |
Occupied |
When 'Keycard' input signal is switched from OFF -> ON and it is in un-occupied mode, FCU will go into the mode. Guest can set a desired temperature by adjusting the touch screen interface in the room. Default: Enabled, last state. (e.g. The last setting before the guest leave the room). |
Interlock |
When 'Window' input signal is switched from ON -> OFF, FCU will go into the mode. System switch FCU to fan mode when window is open. Default: Enabled, Fan mode, Set temperature remain unchanged, Turn-off fan speed. |
Night 1 & 2 |
Two separate night modes driven by Real-time-Clock. Set a specific time to reduce or to increase the temperature especially in midnight period. e.g. From 1am to 5am, setting: No changed for Air-Con mode (Fan / cooling / heating mode), 23oC, Low fan speed . When reached 5am, restore back to the last setting. Default: Disabled. |
The setting of each mode can be set via MODBUS command on the RS-485 port COM0.